B&B Electronics 4 Channel Input Buffer Board SDAIBB Manual de usuario Pagina 32

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 60
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 31
28 Chapter 4 Documentation Number UD128A8D4602 Manual
B&B Electronics Mfg Co 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104
B&B Electronics Ltd Westlink Comm. Pk. Oranmore, Galway, Ireland Ph 353-91-792444 Fax 353-91-792445
Sampling Interval
The Sampling Interval selects how often the I/O points are
updated. The default is 1 second. The minimum interval
is 0.0000625 (62.5usec) for sampling only one analog input, or 0.005
for all 8 analog inputs. To sample more points, the interval
must be increased, because the analog input gets first priority
and all other reads/writes must be interleaved between
the analog reads. The Sampling Interval is used for display
and for the log file.
Vista de pagina 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 59 60

Comentarios a estos manuales

Sin comentarios